Interpretation #8395

Original Request

  • Date: April 20, 2020
  • Requested By: Bob
  • Requester E-Mail: rspears@clermontfl.org
  • Code Version: 2017
  • Code: RESIDENT
  • Code Description:
  • Chapter: Chapter 3 Building Planning
  • Section: 311.3.2
  • Topic: Landings at exterior doors

  • Question: Is a landing required on the exterior side of screen room door?

Answer on 04/20/2020 at 8:10 AM

Screen enclosures are by definition ( a building or part there of... ) so as a building the exterior door is required by FBC R 311.3.2 to have a landing or floor.

Commentary:

Also, note the Exception: A top landing is not required where a stairway of not more than two risers is located on the exterior side of the door. Further, items other than a concrete pad are acceptable to serve as a landing.