While Exceptions 1 and 2 do not seem to apply to this
case, section 1016.1 states the maximum length of exit
access travel is to, among other elements, an exterior
exit stairway, not to the exit discharge. Travel distance
is always measured to the entrance to an exit and that is
what Section 1016.1 requires. Section 1016.1 contemplates
the exterior stair as an exit, not an exit access.
While not enclosed, there are a number of other provisions
of the code addressing exterior stairs as exits and egress
balconies. There are requirements for fire rated separation
from the interior of the building, including opening
protection; the the protection of openings within 10 feet of
the stair;for the percentage of openness on one side; and a
requirement for the arrangement to be such as to restrict
the accumulation of smoke.
In this case, The exit access travel distance of Table
1016.1 is 200 feet. However, Section 1016.2 specifically
permits an increase of up to an additional 100 feet when
using an egress balcony, provided the egress balcony is
constructed in accordance with Section 1019. We are not
provided with those details, but if the construction
complies with Section 1019, the distance to the exterior
stair, not the exit discharge, is permitted to be 300 feet.