Yes, if the work area method is elected. Section 101.5 of
the FBC-EB requires one of three compliance methods be
elected. Under the work area method, this change of
occupancy without change in occupancy classification would
require compliance
with FBC-EB section 908.1, which lists in item #8, health
care facilities as one of the special occupancies which
would require the electrical system to be brought into
compliance with the NEC requirements for the new use.