Question:
Is it the intent of FBC 1009.10 to require railings on both sides of a set of steps that is not a means of egress pathway with 4" risers and 12.5" treads with a total of 14 treads.
Answer on 04/27/2009 at 5:00 PM
Yes. All stairs are required to meet the construction
provisions for means of egress as a matter of occupant
safety.
Commentary:
Florida Building Code - Building Chapter 10 is
titled "MEANS OF EGRESS" not "REQUIRED Means Of Egress".
All stairs are part of a means of egress, perhaps not the
MAIN means of egress but nevertheless a component of egress
from a specific area. Chapter 10 provides the only standard
in the building codes for designing and inspecting any set
of stairs whether the stairs are "required” or
just “convenience” stairs.