Interpretation #9597

Published October 23, 2026

Original Request

Code Version
2023
Code
RESIDENT
Code Description
Chapter
16
Section
M1601.4
Topic
Duct to air handler connection

Question

Is it the intent of Section M1601.4 to require a metal connection along with screws when connecting duct board to an air handler, as shown in SMACNA Figure 4-10 and NAIMA Figure 3-30B, or would a metal listed tape satisfy this requirement?

Answer Published 10/02/2026 at 11:19 AM

Yes, the cited section requires compliance with the stated documents

Commentary

None.