Interpretation #9543

Published June 17, 2026

Original Request

Code Version
2023
Code
MECHANIC
Code Description
Chapter
4
Section
Table 403.3.1.1
Topic
Garage Ventilation Rates

Question

Would the exhaust requirement for the Garage, common for multiple units apply for a single private garage for an apartment home? (It is 1 Garage attached to 1 Apartment home)

Answer Published 06/11/2026 at 8:27 AM

Yes. According to the 2023 FBC, Mechanical, Table 403.3.1.1 garages in both single and private multi-family dwellings require a minimum mechanical exhaust rate of 0.75 cfm per square foot.

Commentary

None.