Interpretation #9501

Published February 24, 2026

Original Request

Code Version
2023
Code
ENERGY
Code Description
Chapter
4
Section
403.2.7
Topic
Hot gas reheat and Exception 7

Question

Does a Hot Gas Reheat coil satisfy the Exception 7 for "Systems requiring dehumidification that employ energy recovery in series with the cooling coil"?

Answer Published 02/20/2026 at 2:18 PM

Yes, systems that require dehumidification can meet the requirement for hot gas reheat by using an energy recovery system in series with the cooling coil.

Commentary

The primary purpose of reheat in HVAC is to independently control space humidity without overcooling the room. By reheating air that has been cooled below its dew point for dehumidification, the system provides dry air at a comfortable, neutral temperature, preventing "cold damp" conditions