Interpretation #8683

Published September 07, 2022

Download Final PDF

Original Request

Code Version
2021
Code
BUILDING
Code Description
Chapter
Section
110.8 and 453.25.6
Topic
Penetrations of Threshold Buildings

Question

Is it the intent of FS 553.79 (5), FBC 453.25.6, and FBC 110.8 to require a threshold inspection plan and a threshold inspector on a bonafide existing threshold building, for a 3/4" electrical conduit penetration or any other similar drilled or cut penetration to an exterior wall for a fire alarm replacement only? Are all exterior envelope penetrations to threshold buildings, no matter how big or small, required to have a threshold inspector?

Answer Published 09/07/2022 at 8:09 AM

Based on FS 553.79(5)(a), It depends if the wall being penetrated is considered part of the structural system or is a structurally load bearing component of the building. This will be determined by AHJ at permitting and either require a threshold inspection plan or not.

Commentary

There is also a declaratory statement, DS 2014-061, which addresses this. A structural alteration to a threshold building must be evaluated on a case-by-case basis by the AHJ. Though a 3/4" hole in a wall might not be considered much of an alteration, drilling through a slab of post-tensioned construction, whether vertical or horizontal, could damage a PT cable, have impacts on fire resistance or pose other implications.