Interpretation #8471

Published November 20, 2020

Download Final PDF

Original Request

Code Version
2017
Code
BUILDING
Code Description
Chapter
Chapter 1-Scope and Administration
Section
107.3.4.2
Topic
plan certification

Question

Is it the intent of 107.3.4.2 to allow a Division 1 contractor that has completed specialized continuing education courses to certify windload and structural design plans and specifications for 1 and 2 family homes that are submitted by any other Division 1 contractor for permitting?

Reference interpretations
7385
5543
7298
4960
Reference statues
489.113.9 (B).2
489.115.4 (B). 2
553.79.17

Answer Published 11/20/2020 at 8:41 AM

Yes. As an Administrative Chapter - this is added to meet the requirements allowed in 489........

Commentary

Certifications by contractors authorized under the provisions of Section 489.115(4)(b), Florida Statutes, shall be considered equivalent to sealed plans and specifications by a person licensed under Chapter 471, Florida Statutes, or Chapter 481, Florida Statutes, by local enforcement agencies for plans review for permitting purposes relating to compliance with the wind resistance provisions of the code or alternate methodologies approved by the Florida Building Commission for one- and two-family dwellings. Local enforcement agencies may rely upon such certification by contractors that the plans and specifications submitted conform to the requirements of the code for wind resistance. If you comply with the following - Certifications by contractors authorized under the provisions of Section 489.115(4)(b), Florida Statute