Interpretation #8378

Published March 16, 2020

Original Request

Code Version
2017
Code
PLUMBING
Code Description
Chapter
Chapter 7 Sanitary Drainage
Section
706.3
Topic
Change of direction from vertical to horizontal

Question

Is the intent of the code to allow a 3” PVC 1/4 bend to be used at the base of a stack?

Answer Published 03/16/2020 at 8:14 AM

Yes, please see the attached commentary.

Commentary

3" PVC 1/4 bends are permitted to be used at the base of a stack (vertical to horizontal.) Drainage fitting nomenclature and geometry are regulated by the referenced fitting standards. In the case of PVC drainage fittings, that standard is ASTM D3311. Quoting from the IPC Commentary, "a fitting of one material will not necessarily be identical to a fitting of another material with the same name. For plastic drainage piping materials, a quarter bend fitting is considered to be "flow equivalent" to a short sweep pattern even though they do not have identical pattern dimensions. This is because the interior of those fittings are much smoother than for cast-iron fittings." It is important, however, not to confuse a "1/4 bend" with a "1/4 bend vent." IPC Commentary Figure 706.3(4) shows the difference.