No. Clarifying - Wrong code book.
If this is a commercial building, Section C403.2.9.6 in the FBC-EC does not allow air handling units in attics of commercial buildings.
Section 603.1.1 has allowances for nonmetallic ducts installed per the FBC-Mech.