Interpretation #8338

Published November 20, 2019

Original Request

Code Version
2017
Code
BUILDING
Code Description
Chapter
Chapter 15- Roof Assemblies and Rooftop Structures
Section
1511.5
Topic
Roof Tile Repairs

Question

is it the intent of FBC 2017-Section 1511.5 to allow roof repairs (less than 25%) with like-kind quality materials, such as tile found in boneyard or salvaged from another slope or building.

Answer Published 11/20/2019 at 1:13 PM

Yes

Commentary

Section 1511.5 mirrors Section 706.5 of the FBC-Existing. In Chapter 3 of the Existing code book (provisions for all compliance methods) Section 302.4 allows for like materials to be permitted for repairs and alterations, provided no unsafe condition is created.