Contact Us   |   Sign In   |   Register

Committee Log In

Interpretation #8301

Original Request

  • Date: July 01, 2019
  • Requested By: Grayson Silver
  • Requester E-Mail: gsilver@bakerbarrios.com
  • Code Version: 2014
  • Code: BUILDING
  • Code Description:
  • Chapter: 7
  • Section: 716.5.2
  • Topic: Fire Curtain

  • Question: Is it the intent of FBC section 716.5 and 716.5.2 to limit the use of opening protectives to fire doors and "metal" fire shutters only or does a 2 hour fire rated perimeter curtain that has been UL 10b and UL 10d certified meet the intent of this section?

Answer on 07/01/2019 at 10:17 AM

No to both questions. Please see the attached commentary

Commentary:

Where allowed by code, Referenced Section is for Fire Door and Shutter Assemblies, there is an assumption that the proposed product to be used, would fall under this category. As such, Section 716.5 has an exception (1) that allows Labeled protective assemblies that conform to the requirements of this section OR UL 10A, UL 14B and UL 14C for Tin-clad fire door assemblies. UL 10D is not in any of the allowance exceptions