The heading of table 1017.2 refers to footnote a. Footnote a clearly states: a. See the following sections for modifications to exit access travel distance requirements. These are not exceptions but modifications to the table that adds additional requirements/restrictions for the specific occupancies. The section referenced for Groups F1 & S1 is section 1017.2.2 which is copied Below. This section limits the maximum 400 foot exit access travel distance to a building that complies with ALL of the requirements listed in this section. This includes the building being one story and the requestor is constructing a 4 story building so they cannot use the 400 foot travel distance allowed by the table.