Interpretation #8035

Original Request

  • Date: November 28, 2017
  • Requested By: Sam West
  • Requester E-Mail: wsamuel@coj.net
  • Code Version: 2014
  • Code: ENERGY
  • Code Description:
  • Chapter: 4
  • Section: C402.4.5.2
  • Topic: Outdoor air intakes and exhausts

  • Question: Section C402.4.5.2 has exceptions to the use of Class 1A motorized dampers. Exception 1 has subheadings for the exception. Does each subheading, (e.g. 1.4), stand by itself as an individual exception? or should all subheadings be taken together, (e.g. 1.1-1.4)?

Answer on 11/28/2017 at 10:07 AM

They must be taken as a group. All apply to use the exception.

Commentary:

None