Interpretation #7845

Published September 30, 2016

Download Final PDF

Original Request

Code Version
2014
Code
BUILDING
Code Description
Chapter
Section
1009.3/1016.3/1021.1/1026
Topic
Exit stairs for open parking garage

Question

On the topmost level of an 8-story open parking structure requiring (2) exits, is it code-compliant to have both exits be unenclosed exit access stairways, with the exit access travel distance measured from the most remote part of the level to the first riser of the stairway?

Answer Published 09/30/2016 at 1:57 PM

No. Please see the attached commentary

Commentary

Once the 6 story limit is reached, the stairs must be enclosed (protected means of egress). However, if the travel distance from the most remote point on the top level to the enclosed stair door on the level below is within the allowable travel distance, the unenclosed stair would be code compliant.