Interpretation #7581

Published August 04, 2015

Original Request

Code Version
2014
Code
EXTBLDG
Code Description
Chapter
Section
Energy - Renovated Bldg
Topic
Energy and renovated buildings

Question

Is it the intent of the Florida Building Code Energy Conservation definition of "Renovated Building" as defined in sections C202 and R202 to include fenestrations and roof covering within the element of the definition, "exterior envelope conditions?" If so, does it constitute an exempted building when the renovation of the fenestration or roof covering is valued under the 30% threshold of the structure's value?

Answer Published 08/04/2015 at 5:14 PM

A Declaratory Statement (DEC Statement) is pending at the

Florida Building Commission. Depending on the outcome of

that issue, this response may change to respond to the

decision made by the Florida Building Commission.



The answer to both questions as it relates to replacement

fenestration is no. Replacement fenestration is called out

as a building component in Section 101.4.7 and is required

to meet the code. In addition, Section R402.3.6 requires all

replacement fenestration to meet the U-factor and SHGC

specified in Table R402.1.1.

Commentary

None