Interpretation #7475

Published April 03, 2015

Download Final PDF

Original Request

Code Version
2007
Code
BUILDING
Code Description
Building
Chapter
10
Section
1014.3
Topic
Travel distance for one exit

Question

Is it the intent of FBC- B Chapter 10 Section 1014.3 to require 100 feet maximum (business/sprinklered) to a point with 2 paths of egress even if this is outside the tenant space of a tenant with only 1 required exit.

Answer Published 04/03/2015 at 11:43 AM

Yes. FBC-B 1021.2 does not allow a single exit from the
third story of B occupancy. When two or more exits are
required, common path of travel must be met.

Commentary

There is no exception to allow common path to not start until you reach the exit access door of the office, so common path calculation begins within the tenant space.