Interpretation #7354

Published July 02, 2014

Original Request

Code Version
2010
Code
BUILDING
Code Description
Building
Chapter
10
Section
1021.2
Topic
Single exit in R2

Question

Is it the intent of section 1021.2 to allow an R-

2 occupancy, three stories, fully sprinklered and

having emergency escape and rescue opening (EERO) sized windows - to also have a single exit to serve four dwelling units- only when there are no more than four dwelling units per story?

Answer Published 07/02/2014 at 4:01 PM

The answer is yes

Commentary

The limit is four dwelling units per floor; not four dwelling units served by the exit. While it is true the text alludes to areas served, it also requires compliance with Table 1021.2 Table 1021.2 specifically says "dwelling units per floor" in the column heading and "4 dwelling units". The table does not say "dwelling units served by the exit". In the example 8 units would exceed the limits of Table 1021.2 and the area served would exceed the allowances of the table. While not identical, this scenario is consistent with the requirements of of the FFPC s.30.2.4.4.