Interpretation #7340

Published June 24, 2014

Original Request

Code Version
2010
Code
BUILDING
Code Description
Building
Chapter
10
Section
1021
Topic
Exits from Dwelling Units

Question

Is it the intent of 1021 exception 4, to allow only one of the two required exits to be acccessible from the dwelling unit, and if that is the intent in a mid rise residential building how is the second exit to be accessed ( rated corridor or elevator lobby?) .

Answer Published 06/24/2014 at 7:16 PM

No.

Commentary

A single means of egress is permitted within and from the unit, but it must provide access to two independent and remote exits (as per section 1014) within the specified travel distance.