Interpretation #7320

Published March 31, 2014

Download Final PDF

Original Request

Code Version
2010
Code
MECHANIC
Code Description
Mechanical
Chapter
3
Section
306.3.2
Topic
Attic Installation

Question

Is it the intent of Section 306.3.2 to require relocation of an air handler to within six(6) feet of an attic access when changing out an existing system?

Answer Published 03/31/2014 at 6:49 PM

No

Commentary

Replacing just the existing split system equipment is typically a level 1 alteration. Section 602.4 in the Existing Building Code requires the new equipment to comply with “materials and methods requirements” of the FBC- Mechanical and FBC- Energy Conservation codes. Section 601.2 in the Existing Building Code will not let you alter the system to make it less energy efficient. Comment: If you are replacing the equipment and reconfiguring or replacing duct system it changes the work to a level 2. The requirements change and the answer becomes yes.