Interpretation #7266

Published October 20, 2013

Original Request

Code Version
2010
Code
PLUMBING
Code Description
Chapter
Section
Appendix F
Topic

Question

Is it the intent of Appendix F, Part 1: General C
1 b, to require professionally designed drawings
for commercial projects to be prepared, signed
and sealed by licensed professionals under
Florida Statutes 471 or 481.

Answer Published 10/20/2013 at 1:34 PM

NO

Commentary

1. First, the Section cited in Appendix F should be 107. The code at Section 107 does not require design by a design professional, but requires such design professional where required by FS 471 or 481. There are specific provisions for specialized items requiring design by a design professional, but not a general requirement. There appears to be no requirement for design of the irrigation system by a landscape architect, unless, the designer is claiming to be a landscape architect. 2. Appendix F is not enforceable unless adopted by a local amendment.