Interpretation #6926

Published February 09, 2012

Original Request

Code Version
2007
Code
BUILDING
Code Description
Building
Chapter
10
Section
1006.2.3.5
Topic
Emergency lighting

Question

Is it the intent of 1006.2.3.5 to require that the emergency lighting system and required illumination be continuous without interruption through the startup of an emergency generator system installed in accordance with FBC and NFPA?

Answer Published 02/09/2012 at 12:08 PM

No. Additionally, 1006.2.2 mandates that 10 second max
change over which in effect creates a mandate for a Type 10
system matching the NFPA 101 language. The battery backup
instant-on lights are not required if the generator can
establish emergency power in ten seconds.

Commentary

The FFPC NFPA 101 section 7.9.2.2 specifies that new emergency power systems for emergency lighting be at least Type 10, Class 1.5, Level 1. This would mean that restoration of power must occur within 10 seconds. As a further note, the high-rise provisions in NFPA 11.8.5.2.1 mandates a minimum Type 60, Class 1, Level 1. Therefore, it appears if the system is providing power to the emergency lighting system, a minimum Type 10, Class 1.5, Level 1 system must be provided.