Interpretation #6891

Published May 29, 2012

Original Request

Code Version
2007
Code
EXTBLDG
Code Description
Existing Building
Chapter
8
Section
807.5.3
Topic
Structural Repairs %

Question

Is it the intent of 807.5.3 that structural repairs which fall under 506.2.1 be counted toward the calculations for determining the overall percentage of actual structural square footage as defined in 807.5.3

Answer Published 05/29/2012 at 3:40 PM

No. A repair(506) is not the same as an alteration. See
202, general definitions for alteration and repair. The
specific description seems closer to a repair than an
alteration, and therefore not governed by 807.

Commentary

Note: If in a flood zone a whole different set of rules apply. The AHJ may have final say on whether or not the extent of replacment is "minor".