Question:
Is it the intent of the exceptions listed in section 607.5.2 to also be applicable to section 607.5.3 without having to add on the exceptions in 607.5.3?
Answer on 12/20/2011 at 9:19 AM
No, the exceptions are limited to the corresponding code
section on partition or barrier.
Commentary:
The cross reference mentioned in the question is not
allowed by the code. There are exceptions that apply for
fire partitions and different exceptions that apply for
fire barriers.