Interpretation #6827

Published August 25, 2011

Download Final PDF

Original Request

Code Version
2007
Code
PLUMBING
Code Description
Plumbing
Chapter
4
Section
403.2
Topic
Separate facilities

Question

We are Designing a multi-tenant warehouse building that consist of small storage bays with the following areas. 1,130 sf storage 126 sf office 58 sf single station toilet room for a total of 1,256 sf. Is it the intent of the code to require separate facilities where such a small area exists and installing the separate facilities would take up approximately 10% of the entire bay.

Answer Published 08/25/2011 at 4:34 PM

Yes, unless one of the exceptions in 403.2 applies.

Commentary

Your example appears to be a storage occupancy with an accessory business occupancy. if so this would not meet one of the exceptions.