Interpretation #6818

Published August 17, 2011

Original Request

Code Version
2007
Code
PLUMBING
Code Description
Plumbing
Chapter
4
Section
403.2
Topic
Separate Facilities

Question

Is it the intent of the Florida Building Code - Plumbing Section 403.2 to require seperate facilities for each sex within individual tenant Bays of a Flex/Space Building. Typical Bay consists of a total of 1,250 sf with 1,125 sf of storage and 125 sf of office with 6 total occupants. Largest Bay consists of a total of 2,975 sf with 2,849 sf of storage and 126 sf of office with 12 total occupants

Answer Published 08/17/2011 at 4:40 PM

Yes, unless one of the exceptions in 403.2 applies.

Commentary

Without knowing what is a "flex/space building" it's difficult to provide a more definite answer. However, the most demanding, strictest or "worst case" approved use for each bay should be used to determine the required facilities.