Interpretation #6529

Original Request

  • Date: May 14, 2010
  • Requested By: R. Harold Law
  • Requester E-Mail: harold.law@mysanibel.com
  • Code Version: 2004
  • Code: BUILDING
  • Code Description: Building
  • Chapter: 15
  • Section: 1510
  • Topic: Reroofing

  • Question: Is it the intent of Florida Building Code - Building Section 1510.2 to require the installation of additional fasteners to secure the roof deck to the roof structural members before installing a new roof covering?

Answer on 05/14/2010 at 11:16 PM

Yes, but not under the code section cited. Re-roofing is
governed under Florida Building Code - Existing Building
Section 611. Depending on the size and spacing of the
existing roof sheathing fasteners, re-nailing may be required.

Commentary:

See Florida Building Code - Existing Building Section 611.7.1, 611.7.1.2 and Table 611.7.1.2 for additional information and re-nailing requirements.