Interpretation #6488

Original Request

  • Date: April 13, 2010
  • Requested By: Jim Paleveda
  • Requester E-Mail: jpaleveda@quorumservices.com
  • Code Version: 2007
  • Code: BUILDING
  • Code Description: Building
  • Chapter: 4
  • Section: 423.1
  • Topic: Educational Facilities

  • Question: Is it the intent of Florida Building Code - Building Section 423.1 to apply the State Requirements for Educational Facilities (SREF) to a charter school operated by and located on the campus of a state community college?

Answer on 04/13/2010 at 3:47 PM

Yes. When charter schools are operated in conjunction with
local school board districts, Florida Building Code -
Building Section 423 and the State Requirements for
Educational Facilities (SREF)are applicable.

Commentary:

The above listed FBC and SREF requirements do not apply to a privately run / operated education facility.