Question:
Is it the intent of the change to R311.4.3 found in the 2005 Supplement to the Florida Building Code, Residential to allow required exit doors to swing out over one or two steps?
Answer on 07/16/2008 at 5:13 PM
Yes. Please see the attached commentary
Commentary:
The Florida Building Commission issued a Declaratory (Dec)
Statement clarifying the issue by stating " ... there is
no requirement in the code that exterior or exit doors
where there is a step down at the doorway be in-swing
doors." The Dec Statement went on to state the Exception
to Section R311.4.3 containing the prohibition of a door
swinging over a landing is to a requirement which was
deleted in the 2005 Supplement. Since the requiremnt was
deleted, the terms of the exception are void. (See DCA06-
DEC-068.)