Interpretation #9587

Published September 28, 2026

Original Request

Code Version
2023
Code
ENERGY
Code Description
Chapter
5
Section
R503
Topic
Mini Split Installation in a Garage

Question

Is there a requirement for an energy 405 form to be provided for a mini split in a garage that is being installed for humidity control? It appears this is only required if the space is being used as a dwelling area, meaning a living space. However, this will remain a garage and will be used for dehumidification control for storage. Is it required or exempt from the 405 form in this case?

Answer Published 09/16/2026 at 8:17 AM

Yes, it is required

Commentary

The proposed work is considered an alteration and R503 requires alterations to comply with the governing rules.