Interpretation #9553

Published July 07, 2026

Original Request

Code Version
2023
Code
RESIDENT
Code Description
Chapter
8
Section
Table R803.2.2
Topic
Minimum Roof Sheathing Thickness

Question

For a project in Wind Exposure C with an actual Ultimate wind speed of 131-mph. Considering a Rafter/Truss Spacing of 24 in. o.c. what is the minimum roof sheathing thickness allowed by the FBC Table R803.2.2?

Answer Published 07/01/2026 at 7:55 AM

Based on table R803.2.2 for a wind speed of 131 mph in Exposure C, the minimum plywood thickness would be 19/32.

Commentary

None.