Interpretation #9534

Published May 20, 2026

Original Request

Code Version
2023
Code
BUILDING
Code Description
Chapter
1
Section
102.2
Topic
Inspections of Docks

Question

Are Docks to be reviewed, permitted and inspected for compliance with the FBC?

Answer Published 05/18/2026 at 9:09 AM

Docks are not exempted from the Florida Building Code under Section 102.2. They are defined as structures, typically supported by piles, served by stairs or ramps, and used to access floating vessels or exiting from recreational water features. If located within a navigable waterway, docks may also be subject to review and approval by the U.S. Army Corps of Engineers. Furthermore, dock utilization is regulated under Section 454.1.11.4 of the Florida Building Code, Building (governing artificial lagoons and surf pools), as well as the Florida Building Code, Accessibility Volume, for recreational boating facilities.

Commentary

Docks and piers that are in floodways shown on FIRMs should be reviewed for floodway encroachment (see your local floodplain management regulations). Electrical requirements and the electrical datum plane needs to be reviewed as well.