Interpretation #9529

Published May 14, 2026

Download Final PDF

Original Request

Code Version
2023
Code
BUILDING
Code Description
Chapter
9
Section
903.2.1.2
Topic
Fire sprinklers for assembly areas

Question

Exception 2 clearly states that in a restaurant sprinklers are not required in fire areas under 200 patrons. That seems to clearly conflict with the FFPC 13.3.2.6.1 which states the load is 100.

Answer Published 04/28/2026 at 12:36 PM

This may be a good topic for a code change to be submitted.

Commentary

If there is statistical data to show why the different numbers were chosen, it would be a good topic of discussion. While many of the conflicts between the philosophy of ICC and NFPA have been corrected, this may be one that still needs to be addressed. There may also be reasons based on construction types and travel distances that the different numbers were chosen. Some research may be indicated