Interpretation #9524

Published May 14, 2026

Original Request

Code Version
2023
Code
ACCSCODE
Code Description
Chapter
6
Section
604.8.2.2
Topic
Clearance at latch/push-side of accessible toilet compartment door

Question

Does the FBC-A 604.8.2.2 requirement for compliance with FBC-A 404 therefore require 12" clearance at the latch/push side of the accessible toilet compartment's self-closing door?

Answer Published 04/28/2026 at 12:30 PM

No. Not for a regular toilet compartment (like with a toilet partition system)

Commentary

Not for a regular toilet compartment and not for an ambulatory accessible toilet compartment. 604.8.2.2 governs ambulatory accessible toilet compartments and figure 604.8.2.2 clearly shows it does not require the 12" clearance. The proper clearance is already built into the wheelchair accessible toilet compartment in 604.8.1.2 and figure 604.8.1.2