Interpretation #9509
Published March 27, 2026
Original Request
- Code Version
- 2023
- Code
- BUILDING
- Code Description
- Chapter
- 10
- Section
- 1010.1.7
- Topic
- Doors in series
Question
Does 1010.1.7 apply to doors within nonaccessible hotel rooms?
Answer Published 03/16/2026 at 3:28 PM
Yes, if the occupancy is R-1, transient (not more than 30 days) such as a hotel. An R-2 non- transient hotel would not need to comply, per 1010.1.7 exception 3.
Commentary
None.