Interpretation #9497

Published February 24, 2026

Download Final PDF

Original Request

Code Version
2023
Code
PLUMBING
Code Description
Chapter
10
Section
1003.3.1
Topic
Grease Interceptor Approved Listings

Question

Is it the intent of section 1003.3.1 to PROHIBIT a dishwasher from wasting into a grease waste piping system if the dishwasher has a pre-rinse sink?

Similarly, does 1003.3.1 prohibit a hand wash sink located within the kitchen from wasting into the grease waste system?

Answer Published 02/20/2026 at 2:05 PM

No. Please see the attached commentary

Commentary

Prerinse sinks are specifically listed in 1003.3.1. Dishwashers without prerinse sinks are also listed; both should be connected. The hand sink, as is not listed, may or may not be required to be connected, dependent on Building Official's examination of documents provided. From the commentary, "The Building Official has the responsibility to define the fixtures and equipment and their intended uses that constitute the need for grease interception." As well, any local utilities requirements that would be above code required should be considered.