Interpretation #9484

Published January 23, 2026

Original Request

Code Version
2023
Code
RESIDENT
Code Description
Chapter
3
Section
R302.2.2
Topic
Fire-retardent-treated roof sheathing under exception for a parapet

Question

Is it the intention of the exception that the 4' of distance for fire-retardent-treated wood sheathing be measured from the centerline of the common 2-hour fire resistance-rated wall assembly? Or, specifically in the case of a rated wall assembly with two walls, that the 4' of distance be measured from the face of the each wall in the assembly?

Answer Published 01/22/2026 at 12:06 PM

From the face of the wall

Commentary

None.