Interpretation #9479

Published January 16, 2026

Original Request

Code Version
2023
Code
ACCSCODE
Code Description
Chapter
Section
Fair Housing Accessibility Guidelines
Topic
Fair housing dwelling unit compliance, under the Florida Building Code

Question

Do the residential units above the parking garage have to meet Fair Housing standards and considered "ground floor units" ?

Answer Published 01/13/2026 at 1:24 PM

No. Units above the ground floor do not meet the definition of covered multifamily dwellings as defined by the FHA if they do not contain four or more units and have an elevator. Any units above the ground level not served by an elevator do not need to meet the Fair Housing accessibility standards.

Commentary

None.