Interpretation #9474

Published December 17, 2025

Original Request

Code Version
2023
Code
ENERGY
Code Description
Chapter
4
Section
402.2.4
Topic
Insulation Retention

Question

According to R402.2.4 Does cardboard baffles qualify as wood-framed or equivalent baffles?

Answer Published 12/12/2025 at 7:59 AM

R402.2.4 requires equivalent protection. This is up to the AHJ to determine, what the code is asking for is protection of loose fill insulation to prevent it entering the living space any time the attic hatch is open, cardboard, OSB, fiberboard or other materials may achieve this and provide equivalency.

Commentary

None.