Interpretation #9472

Published December 15, 2025

Original Request

Code Version
2023
Code
BUILDING
Code Description
Chapter
Section
710.8
Topic
Ducts and air transfer openings

Question

1. Are "duct penetration" and "air transfer opening" two different things?
2. For "smoke partitions", does a "duct penetration" requires a "smoke damper"?

Answer Published 12/12/2025 at 7:53 AM

1. No, they are not the same. "Duct penetrations" refers to ducts passing through a building component (such as walls, partitions, ceilings, etc.) and "Air transfer openings" refers to openings in building components designed to allow air passage, which may even be a framed opening without a door.
2. Yes, a duct penetration through a rated partition requires protection. An air transfer opening in a smoke partition will also require some type of protection.
Florida Building Code (Building), 8th Edition Section 710.8 Ducts and air transfer openings.
The space around a duct penetrating a smoke partition shall be filled with an approved material to limit the free passage of smoke. Air transfer openings in smoke partitions shall be provided with a smoke damper complying with Section 717.3.2.2.
Exception: Where the installation of a smoke damper will interfere with the operation of a required smoke control system in accordance with Section 909, approved alternative protection shall be utilized.

Commentary

None.