Interpretation #9470

Published December 17, 2025

Original Request

Code Version
2023
Code
BUILDING
Code Description
Chapter
16
Section
1612
Topic
Foundation requirements & exceptions for shallow footings instead of piles in Coastal A Zone.

Question

Can a structure be supported by shallow foundations in a coastal a zone?

Answer Published 12/12/2025 at 7:41 AM

No, shallow foundations are not allowed in Coastal A Zones in the State of Florida. Coastal A Zones are defined by Chapter 2, and include the area between the coastal high hazard area (V Zones) or the shoreline, and the inland limit of the Limit of Moderate Wave Action. The Florida Building Code, Section 1612.5(2), 2.1 and 2.2 require that all new construction in Coastal A Zones be elevated on piles or columns and that the bottom of the lowest horizontal structural member must be located at or above the design flood elevation.

Note: ASCE 24 may allow the design professional to design shallow foundations in the Coastal A Zone, but for states that have adopted the International Codes or adopted the flood provisions of the I Codes, shallow foundations are not allowed for new construction within the Coastal A Zone. FEMA Technical Bulletin 9, section 14 provides additional guidance on this subject.

Commentary

None.