Interpretation #9467

Published December 17, 2025

Original Request

Code Version
2023
Code
BUILDING
Code Description
Chapter
1
Section
102.2(h)
Topic
Chickees exemption, allowances

Question

Both section 102.2(h), and F.S. 553.73 exempt a Chickee constructed under the outlined allowance from the requirements of the Florida Building Code. Two questions. This exemption would also exempt this structure from the requirements of the Florida Fire Prevention Code? Second question. If a concrete slab is proposed under the Chickee, but is not physically incorporated (meaning the structure post of the Chickee hut are outside the proposed concrete slab, not imbedded in the slab) would this negate the exemption allowance as the concrete slab would be noted as "incorporated into the structure, and is a nonwood feature"?

Answer Published 12/12/2025 at 7:29 AM

The interpretation of the Florida Fire Prevention Code (FFPC), which generally does not apply to one and two family dwellings, should be requested from the Florida Fire Marshals and Inspectors Association. Question 2, 102.2 (h) specifies "does not incorporate. any electrical, plumbing or non-wood features". Webster defines incorporate as "to blend." It does not specify that it has to be attached to be incorporated. The building volume of the Florida codes does not provide an exemption for the FFPC or concrete. The local fire official should respond to for fire.

Commentary

None.