Interpretation #9460

Published December 01, 2025

Original Request

Code Version
2023
Code
BUILDING
Code Description
Chapter
9
Section
903.4
Topic
Backflow Preventers and Electronic Tamper Switches

Question

In an I-2 occupancy, does the requirement of 903.4 require the control valves of a backflow preventer on a combined fire service/potable water line to have electronic supervision?

Answer Published 11/21/2025 at 8:49 AM

NFPA 25 requires tamper switches and electronic monitoring of all fire sprinkler control valves. This includes the backflow preventer for the fire service as well.

Commentary

It is required unless one of the exceptions is met. In this particular case, Exception 3 may be applicable. "3. Automatic sprinkler systems installed in accordance with NFPA 13R where a common supply main is used to supply both domestic water and the automatic sprinkler system, and a separate shutoff valve for the automatic sprinkler system is not provided."