Interpretation #9159

Published October 03, 2025

Download Final PDF

Original Request

Code Version
2023
Code
BUILDING
Code Description
Chapter
6
Section
603.1 Exception (1)(1.1)
Topic
FRTW in Partitions of Type I & II Construction

Question

Is it the intent of section 603.1, Exception (1)(1.1) to allow every interior nonbearing partition within Type I & II construction, where the nonbearing partition is not required to have fire-resistance rating, allowed to be constructed of FRTW or sheathed with FRTW without having a noncombustible material between the concealed space and the FRTW sheathing?

Answer Published 10/01/2025 at 8:20 AM

The use of FRTW in walls of Types I and II construction has been limited to non load-bearing partitions with a fire-resistance rating of not greater than 2 hours.

Commentary

Exception 1.1 in 603.1 allows the FRTW to be attached directly to studs in assemblies of 2 hour or less. Furthermore, the 1st exception in 718.5 allows that FRTW to be extended into concealed spaces.