Interpretation #9152

Published September 18, 2025

Original Request

Code Version
2023
Code
BUILDING
Code Description
Chapter
10
Section
1004.5
Topic
Areas without fixed seating - Net Floor Area

Question

For the purposes of FBC 1004.5 and Table 1004.5 (Areas without fixed seating, A-2 occupancy with tables and chairs calculated at 15 net square feet per occupant), is aisle space that provides egress travel required to be included in the “net floor area” used to calculate occupant load?

Answer Published 09/16/2025 at 12:58 PM

Yes, it is. The code takes that into consideration to establish the 15 net per square feet per occupant.

Commentary

None.