Interpretation #9151

Published October 03, 2025

Download Final PDF

Original Request

Code Version
2023
Code
BUILDING
Code Description
Chapter
9
Section
903.2.1.2
Topic
Group A-2 Automatic Sprinkler System Exception

Question

For the purposes of FBC 903.2.1.2 Exception, does a bar and lounge where patrons are seated at tables and counters for on-premises consumption of food and drinks qualify as a “restaurant, cafeteria, or similar dining facility,” such that sprinklers would only be required if the occupant load is 200 patrons or more?

Additionally, is the presence of a commercial kitchen with a grill and/or hood a determining factor in whether an establishment qualifies as a “restaurant, cafeteria, or similar dining facility” under this exception?

Answer Published 09/16/2025 at 1:02 PM

As described, this does not meet the exception. A sprinkler system is required.

Commentary

None.