For the purposes of FBC 903.2.1.2 Exception, does a bar and lounge where patrons are seated at tables and counters for on-premises consumption of food and drinks qualify as a “restaurant, cafeteria, or similar dining facility,” such that sprinklers would only be required if the occupant load is 200 patrons or more?
Additionally, is the presence of a commercial kitchen with a grill and/or hood a determining factor in whether an establishment qualifies as a “restaurant, cafeteria, or similar dining facility” under this exception?
Interpretation #9151
Published October 03, 2025
Original Request
- Code Version
- 2023
- Code
- BUILDING
- Code Description
- Chapter
- 9
- Section
- 903.2.1.2
- Topic
- Group A-2 Automatic Sprinkler System Exception
Question
Answer Published 09/16/2025 at 1:02 PM
As described, this does not meet the exception. A sprinkler system is required.
Commentary
None.