Interpretation #9124

Published August 13, 2025

Original Request

Code Version
2023
Code
BUILDING
Code Description
Chapter
1
Section
102.2
Topic
Temporary buildings or sheds used exclusively for construction purposes.

Question

Is the intention of the code to exempt construction office trailers that contain bathroom facilities and are connected temporarily to domestic municipal water supply and sewer from being permitted and inspected for plumbing installations?

Answer Published 07/31/2025 at 10:24 AM

While the temporary building (exception d) or office (exception e) would be exempt Florida Building Code, the temporary connection to any municipal utility would not be exempt.

Commentary

Please note that 102.2 (e) specifically includes the accessibility provisions.