Interpretation #9103

Published July 16, 2025

Download Final PDF

Original Request

Code Version
2023
Code
RESIDENT
Code Description
Chapter
3
Section
302.2
Topic
Fire Separation Walls of Townhomes

Question

Is it the intent of Section 302.2 and/or associated exception, to require that horizontal soffits installed within the first 4-feet on each side of a 2-hour fire separation wall be unvented or otherwise solid in construction?

Answer Published 07/05/2025 at 4:53 PM

No, unvented soffit & fire resistive construction are 2 totally different things.

Commentary

None.