Interpretation #9090

Published August 13, 2025

Download Final PDF

Original Request

Code Version
2021
Code
NEC
Code Description
Chapter
7
Section
760.135 and 760.154
Topic
Power Limited Fire Alarm Circuits

Question

Is it the intent of the NEC (2017) 760.135 and NEC 760.154 to require that the power limited circuit of a fire alarm system only use the cables listed under 760.135 or the substitutions allowed under Table 760.154(A)?

Answer Published 08/06/2025 at 10:47 AM

Cables need to listed to the UL category (CCN) HNIR for use in power limited fire alarm circuits. Fixture wire is not tested to the same standards.

Commentary

None.